2012-05-14 23:16:39 | rev. 1 | CORRECT | No errors, works perfect | APPROVED |
2012-11-09 22:59:01 | rev. 1 | INCORRECT | The wiring is incorrect, it doesn't work on my APC network card2 | APPROVED |
2012-11-29 19:45:11 | rev. 1 | CORRECT | APPROVED | |
2013-02-17 04:43:46 | rev. 1 | CORRECT | Works perfect on the network management 2 card, be sure to turn off software and hardware flow control and use 9600 8N1. 2.5mm plug with PN 274-0298 from Radioshack and a scrapped serial port connector will do the trick. | APPROVED |
2016-03-02 00:50:59 | rev. 1 | CORRECT | APPROVED | |
2016-03-23 21:59:38 | rev. 1 | CORRECT | APPROVED | |
2016-05-16 14:56:37 | rev. 1 | CORRECT | APPROVED | |
2016-06-27 06:44:34 | rev. 1 | CORRECT | APPROVED | |
2017-02-22 18:25:28 | rev. 1 | CORRECT | APPROVED | |
2017-04-05 20:35:49 | rev. 1 | CORRECT | APPROVED | |
2017-04-11 00:51:34 | rev. 1 | CORRECT | APPROVED | |
2018-01-28 00:28:09 | rev. 2 | CORRECT | APPROVED | |
2018-02-05 23:41:34 | rev. 2 | CORRECT | APPROVED | |
2018-03-04 19:49:57 | rev. 2 | CORRECT | APPROVED | |
2018-08-30 14:06:39 | rev. 2 | CORRECT | APPROVED | |
2018-11-27 18:44:48 | rev. 2 | CORRECT | APPROVED | |
2020-06-30 21:10:39 | rev. 3 | CORRECT | APPROVED | |
2020-09-14 16:57:14 | rev. 3 | CORRECT | APPROVED | |
2020-12-22 11:36:04 | rev. 3 | CORRECT | works great, thx | APPROVED |
2021-08-19 00:14:56 | rev. 3 | CORRECT | APPROVED | |
2021-09-08 16:14:23 | rev. 3 | CORRECT | APPROVED | |
2023-01-29 06:34:33 | rev. 3 | ERROR FIXED | In addition to the three pins already listed, a genuine cable (I have one) also has the following pins tied together inside the DB9 hood: 1-4-6 and 7-8. These pins are used to support hardware flow control. | APPROVED |
2023-02-05 11:33:07 | rev. 4 | CORRECT | APPROVED | |
2023-02-05 11:34:11 | rev. 4 | CORRECT | Signal levels are zero to positive voltage only | APPROVED |
2023-02-10 16:40:41 | rev. 5 | CORRECT | APPROVED | |
2023-06-14 06:35:36 | rev. 5 | CORRECT | APPROVED | |
2023-07-14 09:30:42 | rev. 5 | CORRECT | APPROVED | |
2024-01-03 17:38:50 | rev. 5 | CORRECT | APPROVED | |
2024-05-17 13:38:35 | rev. 5 | ERROR FIXED | RX and TX are wrong. TX should be 1 and RX should be 2 on APC side | APPROVED |