| PC Pin name |
PC Pin |
Direction | UPS Pin |
UPS Pin name |
Description |
|---|---|---|---|---|---|
| NC | 1 | ![]() |
1 | NC | |
| AC Power Failuce | 2 | ![]() |
2 | AC Power Failuce | Active negative level (negative impulse indicates a power failure) |
| NC | 3 | ![]() |
3 | NC | |
| Common Ground of Pin 2, 5, 6 | 4 | < > |
4 | Common Ground of Pin 2, 5, 6 | |
| UPS Battery Low | 5 | ![]() |
5 | UPS Battery Low | Active negative level (negative impulse indicates a batery low power level) |
| Turn Off UPS | 6 | ![]() |
6 | Turn Off UPS | Active positive level (positive impulse sent by PC shuts down the UPS) |
| NC / GND for pin 6 | 7 | < > |
7 | NC / GND for pin 6 | NC in Type I cable. GND for pin 6 in Type II cable. |
| NC | 8 | ![]() |
8 | NC | |
| NC | 9 | ![]() |
9 | NC |